Notes on SIMATIC powerrate
5.1 General notes on SIMATIC powerrate
Release Notes
22 Readme, 07/2013, A5E33034906-AA
The example program for S7-300 cannot be downloaded to the IM151-8 PN/DP CPU due to
memory requirements.
Note
Memory requirements of AS blocks
You can find the memory requirements of the AS blocks in the respective manual for
SIMATIC power rat e V4.0 S P2 with PC S
7 or WinCC.
Load management: Adhere to the order for configuring limit violations
To supply the messages with the correct, up-to-date associated values for load
management, pay attention to the data flow of load management in the implementation.
Program the blocks in the correct order of execution.
The "PRE_LMGM" block is called after the "PRE_SUM" or "PR3_SUM" block.
If the blocks are installed in different cyclic interrupt OBs (organization blocks), make sure
that at least one of the two conditions is met:
● You must install " PRE_ SUM" or "PR3_SUM" in the same cyclic interrupt OB as
"PRE_LMGM".
● "You must install PRE_SYNC" or "PR3_SYNC" directly before "PRE_SUM" or
"PR3_SUM" in the same cyclic interrupt OB.
Note
Basics of configuration
Read the detai led infor ma ti on in secti on 2.1 "Bas
ic Configuration" of the Programming and
Operating Manual for SIMATIC powerrate V4.0 SP2 with PCS
7 or WinCC.
Enabling VBA macros for powerrate Reports
You need active VBA macro language support for powerrate Report Tool.
● If you install only Micr osoft O ff ice Excel 2010 , enable in addition the following option:
– Office Shared Features/Visual Basic For Applications.
● If Microsoft Office 2010 is already installed without VBA macros and you open the
PRE_Reports_xlt file template, confirm the prompt to install the VBA macros
retrospectively with "Yes".
If you start the Report Tool without opening the PRE_Reports.xlt, no error message is
displayed and the R ep ort T ool is not init ializ e d
For performance reasons, we recommend that you only publish the process pictures and
Faceplates which are currently needed.