Figure 5. Output ripple voltage for various output voltages with
external 1x22 µF, 2x22 µF ceramic capacitors at the output (2A
load). Input voltage is 12V.
Safety Considerations
For safety agency approval the power module must be installed
in compliance with the spacing and separation requirements of
the end-use safety agency standards, i.e., UL ANSI/UL* 62368-1
and CAN/CSA+ C22.2 No. 62368-1 Recognized, DIN VDE 0868-
1/A11:2017 (EN62368-1:2014/A11:2017).
For the converter output to be considered meeting the
Requirements of safety extra-low voltage (SELV) or ES1, the input
must meet SELV/ES1 requirements. The power module has
extra-low voltage (ELV) outputs when all inputs are ELV.
An input fuse for the module is recommended. Due to the wide
input voltage and output voltage ranges of the module, a 4A,
125Vdc fast acting fuse is recommended
Feature Descriptions
Enable (Remote On/Off)
The NQR002A0X4 2A power modules feature a Enable pin with
positive logic for remote On/Off operation. If the Enable pin is
not being used, leave the pin open (the module will be ON). The
Enable signal (VOn/Off) is referenced to ground. During a Logic High
on the Enable pin, the module remains ON. During Logic-Low,
the module is turned OFF.
Figure 6. Remote On/Off Implementation(positive logic).
Overcurrent Protection
To provide protection in a fault (output overload) condition, the
unit is equipped with internal current-limiting circuitry and can
endure current limiting continuously. At the point of current-limit
inception, the unit enters hiccup mode. The unit operates
normally once the output current is brought back into its
specified range. The average output current during hiccup is 10%
IO, max.
Overtemperature Protection
To provide protection in a fault condition, these modules are
equipped with a thermal shutdown circuit. The unit will shut
down if the overtemperature threshold of 130ºC is exceeded at
the thermal reference point Tref. The thermal shutdown is not
intended as a guarantee that the unit will survive temperatures
beyond its rating. Once the unit goes into thermal shutdown it
will then wait to cool before attempting to restart.
Input Undervoltage Lockout
At input voltages below the input undervoltage lockout limit, the
module operation is disabled. The module will begin to operate
at an input voltage above the undervoltage lockout turn-on
threshold.
Output Voltage Programming
The output voltage of the NQR002A0X4 2A module can be
programmed to any voltage from 0.6dc to 5.5Vdc by connecting
a resistor between the Trim+ and GND pins of the module.
Certain restrictions apply on the output voltage set point
depending on the input voltage. These are shown in the Output
Voltage vs. Input Voltage Set Point Area plot in Fig. 7. The Lower