Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
A
l
l
t
i
d
t
i
l
l
g
ä
n
g
l
i
g
-
A
l
lt
i
d
ö
p
p
e
n
!
A
l
w
a
y
s
a
v
a
i
l
a
b
l
e
-
A
l
w
a
y
s
o
p
e
n
!
www.chscontrols.se
2
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Eaton’s Cutler-Hammer offer a complete range of Moulded
Case Circuit Breakers - MCCBs - 15 - 630 A in three frame
sizes. Each frame size offers a choice of several breaking
capacities up to 100 kA at 400 VAC.
The MCCB:s are designed to conform with all major inter-
national standards including IEC 60947-2 and UL 489/CSA
C22.2 No 5.1. The performance is third party certifi ed by
KEMA, UL and CSA. KEMA, UL and CSA are independent
third party test houses which assure that Eaton’s
Cutler-Hammer MCCB:s meet their exacting standards
through regularly scheduled follow-up testing and inspection.
Innovative design and an optimum of performance
The fl exibility and outstanding performance characteristics of
Eaton’s Cutler-Hammer MCCBs are made possible by the most
logically designed contact assemblies. Based on the patented con-
tact design, the contact assembly creates a high speed ”blow-open”
action when it confronts the electromechanical forces produced by
a high-level fault current.
Cascading and discrimination
The current limiting capacity reduces the rated breaking capacity
required for the other circuit breakers installed downstream.
With Eaton’s Cutler-Hammer MCCBs, a high level of discrimination
in a distribution system is achieved. When a fault occurs, only the
MCCB located immediately upstream is tripped.
Protect IEC/NEC, the new discrimination software, includes the
complete range of protective devices from Eaton’s Cutler-Hammer.
Protect IEC/NEC is easy to use and drastically reduces the time
spent on discrimination studies.
Additional information as cascading rating sheets as well as time/
current curves can be downloaded from our web site,
www.chscontrols.se.
Same MCCBs for IEC and North American applications
Eaton’s Cutler-Hammer Series G MCCBs are for truly global use
with UL/CSA/KEMA-KEUR approvals as standard. Series G MCCBs
are UL 489 listed and meet the requirements in National Electrical
Code (NEC) for “Branch Circuit Protection”, “Motor Branch Circuit
Protection” and as “Disconnecting Means”. Operating mechanism
meets the requirements for mechanical interlocking according to
NFPA 79.
A New Generation of Moulded Case Circuit Breakers
Unmatched protection and fl exibility
All Eaton’s Cutler-Hammer MCCBs are current limiting. High speed
opening and the electromagnetic repulsion forces in combination
with the incorporation of sophisticated arc extinguishing technique
limit energy developed by the short-circuit current to very low
values.
A wide selection of trip units for different applications are available,
thermal-magnetic and Digitrip electronic types, with or without earth
fault protection. Digitrip trip units detect earth fault currents through
residual sensing, they are not designed for zero sequence.
Earth leakage modules, based on zero sequence sensing, with a
built-in current sensor are also available. This technique allows for
protective sensitivities down to 30 mA levels. Earth leakage MCCBs
are available up to 630 A and according to IEC and UL standard.
Information regarding Series G MCCBs 800 - 2500 A
are availabe in a separate cataloge!
H
S
B
E
H
S
E
CC
H
S
E
0
20
40
60
80
100
LG frameJG frameEG frame
Breaking Capacity, Icu at 400 VAC, kA
The MCCBs carry both UL, CSA and KEMA-KEUR certifi cation as standard.
Three frame sizes cover 15 - 630 A, breaking capacity from 18 - 100 kA at 400 VAC
3
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
A Complete System for Unmatched Flexibility...
1
21
20
4
3
2
567
9
8
10
11 12
13
14
16
16
15 17
19
18
22
23 24
25
0
N
0
F
F
I
T
E
S
T
T
E
S
T
test
reset
WARNING
ON/I
T
rip
OFF/O
ON/I
Tr i p
OFF/O
ON
OFF
ON
OFF
O
I
1 Circuit breaker
2 Thermal magnetic trip unit, integrated on EG frame
3 Magnetic only trip unit, integrated on EG frame
4 Electronic protection trip unit, JG/LG frame only
5 Auxiliary/alarm contact
6 Shunt trip
7 Undervoltage release
8 DIN-rail mounting adaptor, EG frame only
9 Plug-in block
10 Terminal cover
11 Terminal end cover
12 Interphase barrier
13 Control wire kit
14 Multiwire connector
15 Steel cable terminal
16 Aluminium/copper terminal
17 Terminal spreader
18 Endcap kit
19 Earth leakage module, side mounted on EG frame
20 Padlockable handle lock hasp
21 Padlockable handle block
22 Motor operator
23 Direct close coupled handle mechanism
24 Through-the-door handle mechanism
25 Flexshaft handle mechanism
4
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Program Overview see note 1, 2, 3, 4, 5, 6
EG frame JG frame LG frame
B E S H E S H C E S H C
Breaking capacity, IEC 60947-2
230 VAC Icu 25 35 85 100 65 85 100 200 65 85 100 200
Ics 25 35 43 50 65 85 100 150 65 85 100 150
400 VAC Icu 18 25 40 70 25 40 70 100 35 50 70 100
Ics 18 25 30 35 25 40 70 75 35 50 70 75
690 VAC Icu 3 4 6 12 12 14 20 12 20 25 35
Ics 3 3 3 6 6 7 10 6 10 13 18
250 VDC Icu 10 10 35 42 10 35 42 42 22 22 42 42
Ics 10 10 35 42 10 35 42 42 22 22 42 42
Breaking capacity, UL 489
240 VAC 25 35 85 100 65 85 100 200 65 85 100 200
480 VAC 18 25 35 65 25 35 65 100 35 50 65 100
600Y/347 VAC 18 22 25
600 VAC 18 25 35 50 18 25 35 50
General
Rated voltage Ue IEC 60947-2, V 500, 690 690 690
Rated voltage UL 489, V 480, 600Y/347 600 600
Current range In, A 15 - 125/160 20 - 250 100 - 600/630
Utilization category, IEC 60947-2 A A A
Trip units
Type Fixed trip units Interchangeable trip units Interchangeable trip units
Thermal magnetic FT-FM, AT-FM FT-AM, AT-AM FT-AM, AT-AM
Magnetic only, starter combination AM AM AM
Electronic LS, LSI, LSG, LSIG LS, LSI, LSG, LSIG
Notes
1 125 A is max UL rating for EG frame. 600 A is max UL rating for LG frame.
2 DC ratings are based on two poles in series.
3 MCCBs with ”Straight voltage rating” have been tested for use in a circuit where the nominal voltage between any two conductors does not exceed the voltage rating
of the MCCB. The slash (/) between the higher and lower voltage ratings indicates that the MCCB has been tested for use in a circuit with higher voltage between
phases and with the lower voltage to ground. EG-frame MCCBs have been tested for 600Y/347 and 480 V Straight per UL 489. Contact CHS Controls for application
assistance.
4 See page 20 for breaking capacity for starter combination breakers.
5 Available protection types. Curves are available at www.chscontrols.se.
FT-FM Fixed thermal, fi xed magnetic LS Long delay and short delay protection
AT-FM Adjustable thermal, fi xed magnetic LSI Long delay, short delay and instantaneous protection
FM-AM Fixed thermal, adjustable magnetic LSG Long delay, short delay and earth fault protection
AT-AM Adjustable thermal, adjustable magnetic LSIG Long delay, short delay, instantaneous and earth fault protection
AM Adjustable magnetic, starter combination
6 Electronic trip units are not suitable for DC applications.
5
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Technical Data Moulded Case Circuit Breakers
Frame size EG JG LG
General
Current range, In IEC 60947-2, A 16-160 20-250 70-630
Current range, In UL 489, A 15-125 20-250 70-600
Utilization category, IEC 60947-2 A A A
Number of poles 1, 2, 3, 4 2, 3, 4 3, 4
Rated operational voltage, Ue, IEC 60947-2, V 500, 690 690 690
Rated operational voltage, Ue, UL 489, V 480, 600Y/347 600 600
Rated insulation voltage, Un, IEC 60947-2, V 690 750 750
Rated impulse withstand voltage, Uimp, IEC 60947-2, kV 6 8 8
Breaking Capacity
IEC 60947-2 See product overview on page 4 and product selection
UL 489 See product overview on page 4 and product selection
Moulded Case Switch (MCS)
Breaking capacity at 415 VAC, unfused, kA 70 70 70
Breaking capacity at 480 VAC, unfused, kA 65 65 65
Self protected, will trip above, A 1250/1600 2500 4000/6300
Environmental
Permissible ambient temperature, °C -20 - +70 -20 - +70 -20 - +70
Power losses, plant protection/isolating/starter combination, W 50/40/40 75/75/45 255/160/160
Operation, Endurance
Main switch characteristic, IEC 60947-2 Yes, in combination with locable rotary device
Suitable for reverse feed see note 7 Yes Yes Yes
Opening time, ms <50 <50 <50
Maximum switching frequency, operation/hour 300 240 240
Endurance, operating cycles 10000 10000 80000
Permissible Loads for Various Ambient Temperatures
MCCBs for plant protection see note 8 At 40°C 100/100% 100 /100% 100 /100%
At 50°C 96/92% 96/94% 96/91%
At 55°C 93/87% 94/90% 93/86%
At 6C 91/83% 92/87% 90/82%
At 7C 86/73% 88/80% 84/70%
MCCBs for starter combinations/MCS At 4C 100% 100% 100%
At 5C 100% 100% 100%
At 55°C 96% 96% 95%
At 60°C 91% 92% 90%
At 70°C 86% 88% 84%
Permissible Mounting Positions
Weights
3 pole, kg 1,4 5,2 7,3
4 pole, kg 1,8 7 9,1
Approvals
KEMA-KEUR Certi cate No 2012668.09 2012668.12 Pending, available in June 2005
MCCBs for plant protection only
UL 489/508/1076 File E7819 E7819 E7819
CSA C22.2 File LR43556 LR43556 LR43556
Notes
7 EG frame MCCB for starter combinations (HMCPE) can not be used for reverse feed
8 First fi gure: thermal trip set to the lower value, second fi gure: thermal trip set to the upper value.
09 °
0
9°
09 °
09 °
6
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Technical Data - Electronic Trip Units see note 6, 9
LS protection LSG protection LSI protection LSIG protection
Sensing method RMS RMS RMS RMS
Overtem perature protec tion Yes Yes Yes Yes
Overload protection, long time delay (L)
Long delay setting, Ir 0,5-1 x In 0,5-1 x In 0,5-1 x In 0,5-1 x In
Long delay time I2t at 6 x Ir 2-24 s 2-24 s 2-24 s 2-24 s
Long delay thermal memory Yes Yes Yes Yes
Short circuit protection, short time delay (S)
Short delay setting 200-800% x In 200-800% x In 200-800% x In 200-800% x In
Short delay time I2t 100 ms 100 ms No No
Short delay time at No No I-300 ms I-300 ms
Short circuit protection, instantaneous (I)
Instantaneous setting
see note 10 No No 200-800% x In 200-800% x In
Instantaneous override Yes Yes Yes Yes
Eath fault protection (G)
Earth fault protection No Yes No Yes
Earth fault delay, fl at No I, 120 ms No I, 120 ms
Field testing External test set External test set External test set External test set
DC Applications
The MCCBs with thermal magnetic trip units are suitable for switching DC
currents. MCCBs with electronic trip units should not be used.
For switching DC currents, however the maximum permissible voltage per
conducting path has to be considered.
For voltages higher than 250 VDC, the series connection of two or three
Double-pole switching
max 250 VDC
If there is no risk of an earth fault,
or if any earth fault which occurs is
immediately eliminated (earth fault
monitoring), the max permissible
voltage can be 600 VDC.
conducting paths are required, see proposed circuits for 3 and 4 pole
MCCBs below.
As the current has to fl ow through all conducting paths so as to maintain
the thermal tripping characteristics, the following circuit arrangements are
recommended. With DC, the trip values of the instantaneous short circuit
release is increased by 30 - 40%.
Double-pole switching - earth
system, max 440 VDC
The earthed pole must always
be assigned to the individual
conducting path, so that two paths
are always in series in case of an
earth fault.
Single-pole switching - earth
system, max 600 VDC
Three conducting paths in
series. The earthed pole must
be assigned to the nonswitched
conducting path.
Single-pole switching - earth
system, max 750 VDC
Four conducting paths in series.
The earthed pole must be
assigned to the nonswitched
conducting path.
Notes
6 Electronic trip units are not suitable for DC applications.
9 Curves are available at www.chscontrols.se.
10 JG frame has also a 1400% setting.
MM M M
7
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Technical Data - Auxiliary/Alarm Switches
General
Rated thermal current, Ith, A 6
Rated making capacity, A 20
Rated insulating voltage Un, V 690
Rated impulse withstand voltage Uimp, kV 4
Electrical Data, Utilization Category AC-15, IEC 60947-5-1
Rated operational voltage, VAC 230/400/600
Rated operational current, A 6/3/0,25
Back up fuse class gG 6/4/4
Miniature circuit breaker, B-curve 6/4/-
Electrical Data, Utilization Category DC-13, IEC 60947-5-1
Rated operational voltage, VDC 125/250
Rated operational current, A 0,5/0,25
Back up fuse class gG 6/4
Miniature circuit breaker, B-curve 6/4
Technical Data - Shunt Trip/Undervoltage Trip
Shunt Trip
Response voltage, pick-up, Us 70 - 110%
Opening time <50 ms
Power consumption short time operation
120 VAC <435 VA
240 VAC <435 VA
380-600 VAC <1050 VA
24 VDC <635 W
48 VDC <1580 W
Undervoltage Release
Response voltage, drop Us 35-70%
Response voltage, pick-up, Us 85-110%
Opening time <50 ms
Power consumption, continuous operation
24 VAC <4 VA
48 VAC <4 VA
120 VAC <2,5 VA
208 - 240 VAC <4 VA
380 - 500 VAC <6 VA
525 - 600 VAC <4,5 VA
24 VDC <3,1 W
48 VDC <3,1 W
120 VDC <2,2 W
220-250 VDC <4 W
Internal Accessories
Series G MCCBs can be equipped with a number of internal accessories,
auxiliary switches, alarm switches, shunt trip and undervoltage release.
Auxiliary switches
Available with one or two changeover contacts. They indicate if the MCCB
is in closed or open position.
Alarm switches
Available with one or two changeover contacts. They indicate if the MCCB
is in tripped position.
Combination switches
Consist of one changeover alarm switch and one changeover auxiliary
contact.
Shunt trip
Shunt trip is used for remote tripping of the MCCB. The shunt trip coil is
only rated for short time operation and should not be used in control cir-
cuits with a continuous command. The shunt trip has built-in cut-off switch
to prevent coil burnout.
Undervoltage release
The MCCB can not be closed until the undervoltage release is energized.
If the undervoltage release is not energized, the MCCB can only perform
an idle switching operation. Idle operation should be avoided as they
shorten the endurance of the MCCB.
U<
U<
U<
U<
U<
U<
U< 1 AS + 1 AUX
1/2 AS
1/2 AUX
1/2 AUX
1/2 AS
1 AS + 1 AUX
Contact position by the auxiliary and alarm switches as a function of the switching
position of the MCCB
Off/Reset
On
Tripped
MCCB Toggle
position
Auxiliary switch
position
Alarm switch
position
Shunt trip/undervoltage release AUX = Auxiliary switch AS = Alarm switch
Accessory alternatives - one of above combinations, insulated accessory chambers
3 pole MCCB 4 pole MCCB
Left Right Left Right
8
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Moulded Case Circuit Breakers for Plant Protection, EG Frame 15 - 160 A, IEC/UL/CSA
Breaker Capacity see note 3, 11
Breaking capacity, kA
Breaker Rated voltage, Ue, VAC IEC 60947-2, Icu/Ics, VAC UL 489/CSA, VAC
type IEC UL/CSA 230 400 690 240 480 600Y/347
B 500 480 25/25 18/18 25 18
E 500, 690 600Y/347 35/35 25/25 3/3 35 25 18
S 500, 690 600Y/347 85/43 40/30 4/3 85 35 22
H 500, 690 600Y/347 100/50 70/35 6/3 100 65 25
Catalogue Numbers, 3 Pole MCCB with Thermal-Magnetic Trip Unit see note 12, 13, 14, 15, 16, 17
Rated Adjustable range
current Thermal Magnetic Catalogue numbers, complete breakers
In, A Ir, A Im, A Type B Type E Type S Type H
15 Fixed Fixed EGB3015FFG EGE3015FFG EGS3015FFG EGH3015FFG
16 Fixed Fixed EGB3016FFG EGE3016FFG EGS3016FFG EGH3016FFG
20 Fixed Fixed EGB3020FFG EGE3020FFG EGS3020FFG EGH3020FFG
25 Fixed Fixed EGB3025FFG EGE3025FFG EGS3025FFG EGH3025FFG
30 Fixed Fixed EGB3030FFG EGE3030FFG EGS3030FFG EGH3030FFG
32 Fixed Fixed EGB3032FFG EGE3032FFG EGS3032FFG EGH3032FFG
35 Fixed Fixed EGB3035FFG EGE3035FFG EGS3035FFG EGH3035FFG
40 Fixed Fixed EGB3040FFG EGE3040FFG EGS3040FFG EGH3040FFG
45 Fixed Fixed EGB3045FFG EGE3045FFG EGS3045FFG EGH3045FFG
50 Fixed Fixed EGB3050FFG EGE3050FFG EGS3050FFG EGH3050FFG
60 Fixed Fixed EGB3060FFG EGE3060FFG EGS3060FFG EGH3060FFG
63 Fixed Fixed EGB3063FFG EGE3063FFG EGS3063FFG EGH3063FFG
70 Fixed Fixed EGB3070FFG EGE3070FFG EGS3070FFG EGH3070FFG
80 Fixed Fixed EGB3080FFG EGE3080FFG EGS3080FFG EGH3080FFG
90 Fixed Fixed EGB3090FFG EGE3090FFG EGS3090FFG EGH3090FFG
100 Fixed Fixed EGB3100FFG EGE3100FFG EGS3100FFG EGH3100FFG
125 Fixed Fixed EGB3125FFG EGE3125FFG EGS3125FFG EGH3125FFG
160 Fixed Fixed EGB3160FFG EGE3160FFG EGS3160FFG EGH3160FFG
20 16-20 Fixed EGB3020AFG EGE3020AFG EGS3020AFG EGH3020AFG
25 20-25 Fixed EGB3025AFG EGE3025AFG EGS3025AFG EGH3025AFG
32 25-32 Fixed EGB3032AFG EGE3032AFG EGS3032AFG EGH3032AFG
40 32-40 Fixed EGB3040AFG EGE3040AFG EGS3040AFG EGH3040AFG
50 40-50 Fixed EGB3050AFG EGE3050AFG EGS3050AFG EGH3050AFG
63 50-63 Fixed EGB3063AFG EGE3063AFG EGS3063AFG EGH3063AFG
80 63-80 Fixed EGB3080AFG EGE3080AFG EGS3080AFG EGH3080AFG
100 80-100 Fixed EGB3100AFG EGE3100AFG EGS3100AFG EGH3100AFG
125 100-125 Fixed EGB3125AFG EGE3125AFG EGS3125AFG EGH3125AFG
125 Moulded case switch EGK3125KSG
160 125-160 Fixed EGB3160AFG EGE3160AFG EGS316AFFG EGH3160AFG
160 Moulded case switch EGK3160KSG
9
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Catalogue Numbers, 4 Pole MCCB with Thermal-Magnetic Trip Unit see note 12, 13, 14, 15, 16, 17, 18
Rated Adjustable range
current Thermal Magnetic Catalogue numbers, complete breakers
In, A Ir, A Im, A Type B Type E Type S Type H
15 Fixed Fixed EGB4015FFG EGE4015FFG EGS4015FFG EGH4015FFG
16 Fixed Fixed EGB4016FFG EGE4016FFG EGS4016FFG EGH4015FFG
20 Fixed Fixed EGB4020FFG EGE4020FFG EGS4020FFG EGH4020FFG
25 Fixed Fixed EGB4025FFG EGE4025FFG EGS4025FFG EGH4025FFG
30 Fixed Fixed EGB4030FFG EGE4030FFG EGS4030FFG EGH4030FFG
32 Fixed Fixed EGB4032FFG EGE4032FFG EGS4032FFG EGH4032FFG
35 Fixed Fixed EGB4035FFG EGE4035FFG EGS4035FFG EGH4035FFG
40 Fixed Fixed EGB4040FFG EGE4040FFG EGS4040FFG EGH4040FFG
45 Fixed Fixed EGB4045FFG EGE4045FFG EGS4045FFG EGH4045FFG
50 Fixed Fixed EGB4050FFG EGE4050FFG EGS4050FFG EGH4050FFG
60 Fixed Fixed EGB4060FFG EGE4060FFG EGS4060FFG EGH4060FFG
63 Fixed Fixed EGB4063FFG EGE4063FFG EGS4063FFG EGH4063FFG
70 Fixed Fixed EGB4070FFG EGE4070FFG EGS4070FFG EGH4070FFG
80 Fixed Fixed EGB4080FFG EGE4080FFG EGS4080FFG EGH4080FFG
90 Fixed Fixed EGB4090FFG EGE4090FFG EGS4090FFG EGH4090FFG
100 Fixed Fixed EGB4100FFG EGE4100FFG EGS4100FFG EGH4100FFG
125 Fixed Fixed EGB4125FFG EGE4125FFG EGS4125FFG EGH4125FFG
160 Fixed Fixed EGB4160FFG EGE4160FFG EGS4160FFG EGH4160FFG
20 16-20 Fixed EGB4020AFG EGE4020AFG EGS4020AFG EGH4020AFG
25 20-25 Fixed EGB4025AFG EGE4025AFG EGS4025AFG EGH4025AFG
32 25-32 Fixed EGB4032AFG EGE4032AFG EGS4032AFG EGH4032AFG
40 32-40 Fixed EGB4040AFG EGE4040AFG EGS4040AFG EGH4045AFG
50 40-50 Fixed EGB4050AFG EGE4050AFG EGS4050AFG EGH4050AFG
63 50-63 Fixed EGB4063AFG EGE4063AFG EGS4063AFG EGH4063AFG
80 63-80 Fixed EGB4080AFG EGE4080AFG EGS4080AFG EGH4080AFG
100 80-100 Fixed EGB4100AFG EGE4100AFG EGS4100AFG EGH4100AFG
125 100-125 Fixed EGB4125AFG EGE4125AFG EGS4125AFG EGH4125AFG
160 125-160 Fixed EGB4160AFG EGE4160AFG EGS416AFFG EGH4160AFG
Notes
3 MCCBs with ”Straight voltage rating” have been tested for use in a circuit where the nominal voltage between any two conductors does not exceed the voltage rating
of the MCCB. The slash (/) between the higher and lower voltage ratings indicates that the MCCB has been tested for use in a circuit with higher voltage between
phases and with the lower voltage to ground. EG-frame MCCBs have been tested for 600Y/347 and 480 V Straight per UL 489. Contact CHS Controls for application
assistance.
11 690 VAC rating only apply to 160 A MCCBs.
12 Contact CHS Controls for 1-pole and 2-pole MCCBs.
13 Replace suf x ”G” with ”W” for no line and load terminals. Example: EGB3100FAG will be EGB3100FAW
14 The MCCBs are calibrated at 40°C ambient temperature. MCCBs calibrated for 50°C ambient temperature are also available, add suffi x ”V” to the end
of the catalogue number. Example: EGB3100FAG will be EGB3100FAGV. 50°C calibrated MCCBs are not UL/CSA approved. MCCBs with electronic trip units can
operate reliably at 50°C ambient temperature.
15 16, 32, 63 and 160 A MCCBs as well as MCCBs with adjustable thermal trip are not UL/CSA approved.
16 Moulded case switches are self protected, see page 5 for trip levels.
17 M4 hardware is included.
18 4 pole MCCBs have unprotected neutral. Replace the fourth character by ”7” for 100% protected neutral. Example: EGB4100FAG will be EGB7100FAG.
10
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Earth Leakage Modules for EG Frame MCCBs, Side Mounted
Rated Rated
current voltage Pickup Time Alarm contacts
In, A Un, VAC Poles Standard setting, A Delay, s Earth fault level Catalogue numbers
125 230-415 3 IEC 0,03-10 Inst.-1 50/100% ELEBLE3125W
125 230-415 4 IEC 0,03-10 Inst.-1 50/100% ELEBE4125W
Terminals, Installation Accessories for EG Frame MCCBs see note 19, 20, 21
Description Catalogue numbers
Terminals for Cu/Al cond., pressure type, 125 A, 2,5-95 mm2/AWG 14-3/0, kit of 3 3T125EF, included
Terminals for Cu/Al cond., pressure type, 125 A, 2,5-50 mm2/AWG 14-1/0, kit of 3 3TA125EF
Terminals for Cu/Al cond., pressure type, 160 A, 16-70 mm2/AWG 6-3/0, kit of 3 3TA150EF, included
Terminals for Cu/Al cond., pressure type, 160 A, 35-120 mm2/AWG-kcmil 3-250, kit of 3 3TA160EFK
Terminals for Cu/Al cond., pressure type, 160 A, 35-120 mm2/AWG-kcmil 3-250, kit of 4 4TA160EFK
Endcap kit for busbar/cable lugs, 3 pole, metric hardware EF3RTWK
Endcap kit for busbar/cable lugs, 4 pole, metric hardware EF4RTWK
Endcap kit for busbar/cable lugs, 3 pole, imperial hardware EF3RTDK
Endcap kit for busbar/cable lugs, 4 pole, imperial hardware EF4RTDK
Multiwire connectors for Cu cond., 125 A, 3 wires, 2,1-13 mm2/AWG 14-6, kit of 3 3TA100E3K
Multiwire connectors for Cu cond., 125 A, 6 wires, 2,1-13 mm2/AWG 14-6, kit of 3 3TA100E6K
Control wire terminal kit, only for use with 3T125EF terminals, 12 pcs per package GCWTK
Spreader, pole cc=35,4 mm, 3 pole, hardware not included, use endcap kit EFTEW3
Spreader, pole cc=35,4 mm, 4 pole, hardware not included, use endcap kit EFTEW4
Terminal shields, ingress protection IP 30, 3 pole EFTS3K
Terminal shields, ingress protection IP 30, 4 pole EFTS4K
Terminal end cover, 3 pole, conductor opening 6,4 mm, 10 pcs per package EEC3K
Terminal end cover, 3 pole, conductor opening 10,4 mm, 10 pcs per package EEC4K
Interphase barriers, 2 pcs per package EIPBK
Mounting adapter for 35mm DIN rail, for 3 pole and 4 pole MCCBs EF34DIN
Plug-in Blocks for EG Frame Breakers see note 22
Plug-in block for 3 pole breaker, including breaker terminals and trip-on drawout interlock PAD3E
Plug-in block for 4 pole breaker, including breaker terminals and trip-on drawout interlock PAD4E
Notes
19 3TA160EFK and 4TA160EFK, terminal cover is included.
20 Multiwire terminals only to be used on 3 pole MCCBs, terminal cover is included.
21 Terminal 3T125EF is made of steel. Terminals 3TA125EF, 3TA150EF, 3TA160EFK and 4TA160EFK are made of aluminium.
22 Plug-in block can be installed either on or partly behind mounting plate. Rear terminal stabs are included. Stabs can be converted to front terminals.
reset
test
3T125EF 3TA125EF 3TA150EF
3TA160EFK Endcap kit
Multiwire teminal GCWTK
Spreader Interphase barrier
Terminal shield
Terminal end cover
11
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Internal Accessories for EG Frame MCCBs see note 23
Description Catalogue Number
Auxiliary contact, 1 change-over contact AUX1A1BPK
Auxiliary contact, 2 change-over contacts AUX2A2BPK
Alarm contact, 1 change-over contact ALM1M1BEPK
Alarm contact, 2 change-over contacts ALM2M2BEPK
Combination auxiliary and alarm contact, 1 change-over contact of each AUXALRMEPK
Shunt trip, 120 VAC SNT120CPK
Shunt trip, 240 VAC SNT120CPK
Shunt trip, 380-600 VAC SNT480APK
Shunt trip, 24-48 VDC SNT060CPK
Undervoltage release, 120 VAC UVR120APK
Undervoltage release, 208-240 VAC, 380-500 VAC UVR480APK
Undervoltage release, 525-600 VAC UVR600APK
Undervoltage release, 24 VAC/VDC UVR024CPK
Undervoltage release, 48 VAC UVR048APK
Undervoltage release, 48 VDC UVR048DPK
Undervoltage release, 120 VDC UVR125DPK
External Accessories for EG Frame MCCBs see note 24, 25, 26
Direct (close-coupled) rotary handle EHMCCB
Direct (close-coupled) rotary handle with door interlock EHMCCBI
Rotary through-the-door handle, black - IP 54/NEMA 12, 152 mm shaft EHMVD06B
Rotary through-the-door handle, black - IP 54/NEMA 12, 304 mm shaft EHMVD12B
Rotary through-the-door handle, black - IP 54/NEMA 12, 609 mm shaft EHMVD24B
Rotary through-the-door handle, red - IP 54/NEMA 12, 152 mm shaft EHMVD06R
Rotary through-the-door handle, red - IP 54/NEMA 12, 304 mm shaft EHMVD12R
Rotary through-the-door handle, red - IP 54/NEMA 12, 609 mm shaft EHMVD24R
Rotary through-the-door handle, black - IP 65/NEMA 4X, 152 mm shaft EHMVD06BX
Rotary through-the-door handle, black - IP 65/NEMA 4X, 304 mm shaft EHMVD12BX
Rotary through-the-door handle, black - IP 65/NEMA 4X, 609 mm shaft EHMVD24BX
Rotary through-the-door handle, red - IP 65/NEMA 4X, 152 mm shaft EHMVD06RX
Rotary through-the-door handle, red - IP 65/NEMA 4X, 304 mm shaft EHMVD12RX
Rotary through-the-door handle, red - IP 65/NEMA 4X, 609 mm shaft EHMVD24RX
Flexshaft mechanism, fl ange mounted handle - IP 54/NEMA 12, 1,2 m wire EHMFS04
Flexshaft mechanism, fl ange mounted handle - IP 54/NEMA 12, 2,1 m wire EMHFS07I
Flexshaft mechanism, fl ange mounted handle - IP 65/NEMA 4X, 1,2 m wire EHMFS04X
Flexshaft mechanism, fl ange mounted handle - IP 65/NEMA 4X, 2,1 m wire EHMFS07X
Motor operator, 120 VAC EOPEF240C
Motor operator, 240 VAC EOPEF240C
Motor operator, 24 VDC EOPEF24D
Motor operator, 48 VDC EOPEF48D
Motor operator, 120 VDC EOPEF240C
Handle block for temporary use, padlockable in On/Off position EFPHB
Handle block for temporary use, padlockable in Off position EFPHBOFF
Handle block, fi xed mounted on breaker, padlockable in On/Off position EFPHL
Handle block, fi xed mounted on breaker, padlockable in Off position EFPHLOFF
Discrimination/system design software on CD Contact CHS Controls
Notes
23 See page 7 for possible installation combinations.
24 Rotary through-the-door handle, see page 24 for min and max enclosure depth.
25 Flexshaft mechanism, additional hardware may be required depending on enclosure type. Contact CHS Controls for more information.
26 Contact CHS Controls for breaker interlock kits and cylinder locks.
ON/I
T
rip
OFF/O
ON/I
T
rip
OFF/O
ON
OFF
ON
OFF
O
I
Direct rotary handle
Rotary through-the-door handle
Flexshaft mechanism, fl ange mounted
Motor operator
Handle block Handle block
xed mounted temporary use
Aux/alarm switch
Shunt trip
Undervoltage release
12
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Moulded Case Circuit Breakers for Plant Protection, JG Frame 63 - 250 A, IEC/UL/CSA
Breaker Capacity
Breaking capacity , kA, VAC
Breaker Rated voltage, Ue, VAC IEC 60947-2, Icu/Ics UL 489/CSA
type IEC UL/CSA 230 400 690 240 480 600
E 690 600 65/65 25/25 12/6 65 25 18
S 690 600 85/85 40/40 12/6 85 35 25
H 690 600 100/100 70/70 14/7 100 65 35
C 690 600 200/150 100/75 20/10 200 100 50
Catalogue Numbers, MCCBs with Thermal-Magnetic Trip Unit see note 17, 27, 28, 29, 30
Rated Adjustable range Catalogue numbers
current Thermal Magnetic Complete breakers Trip unit
In, A Ir, A Im, A Type E Type S Type H Type C only
3 pole breakers
70 Fixed 350-700 JGE3070FAG JGS3070FAG JGH3070FAG JGC3070FAG JT3070FA
90 Fixed 450-900 JGE3090FAG JGS3090FAG JGH3090FAG JGC3090FAG JT3090FA
100 Fixed 500-1000 JGE3100FAG JGS3100FAG JGH3100FAG JGC3100FAG JT3100FA
125 Fixed 625-1250 JGE3125FAG JGS3125FAG JGH3125FAG JGC3125FAG JT3125FA
150 Fixed 750-1500 JGE3150FAG JGS3150FAG JGH3150FAG JGC3150FAG JT3150FA
175 Fixed 875-1750 JGE3175FAG JGS3175FAG JGH3175FAG JGC3175FAG JT3175FA
200 Fixed 1000-2000 JGE3200FAG JGS3200FAG JGH3200FAG JGC3200FAG JT3200FA
225 Fixed 1125-2250 JGE3225FAG JGS3225FAG JGH3225FAG JGC3225FAG JT3225FA
250 Fixed 1250-2500 JGE3250FAG JGS3250FAG JGH3250FAG JGC3250FAG JT3250FA
80 64-80 400-800 JGE3080AAG JGS3080AAG JGH3080AAG JGC3080AAG JT3080AA
100 80-100 500-1000 JGE3100AAG JGS3100AAG JGH3100AAG JGC3100AAG JT3100AA
125 100-125 625-1250 JGE3125AAG JGS3125AAG JGH3125AAG JGC3125AAG JT3125AA
160 128-160 800-1600 JGE3160AAG JGS3160AAG JGH3160AAG JGC3160AAG JT3160AA
200 160-200 1000-2000 JGE3200AAG JGS3200AAG JGH3200AAG JGC3200AAG JT3200AA
250 200-250 1250-2500 JGE3250AAG JGS3250AAG JGH3250AAG JGC3250AAG JT3250AA
250 Breaker frame only JGE3250NN JGS3250NN JGH3250NN
250 Moulded case switch JGK3250KSG
4 pole breakers
70 Fixed 350-700 JGE4070FAG JGS4070FAG JGH4070FAG JGC4070FAG JT4070FA
90 Fixed 450-900 JGE4090FAG JGS4090FAG JGH4090FAG JGC4090FAG JT4090FA
100 Fixed 500-1000 JGE4100FAG JGS4100FAG JGH4100FAG JGC4100FAG JT4100FA
125 Fixed 625-1250 JGE4125FAG JGS4125FAG JGH4125FAG JGC4125FAG JT4125FA
150 Fixed 750-1500 JGE4150FAG JGS4150FAG JGH4150FAG JGC4150FAG JT4150FA
175 Fixed 875-1750 JGE4175FAG JGS4175FAG JGH4175FAG JGC4175FAG JT4175FA
200 Fixed 1000-2000 JGE4200FAG JGS4200FAG JGH4200FAG JGC4200FAG JT4200FA
225 Fixed 1125-2250 JGE4225FAG JGS4225FAG JGH4225FAG JGC4225FAG JT4225FA
250 Fixed 1250-2500 JGE4250FAG JGS4250FAG JGH4250FAG JGC4250FAG JT4250FA
80 64-80 400-800 JGE4080AAG JGS4080AAG JGH4080AAG JGC4080AAG JT4080AA
100 80-100 500-1000 JGE4100AAG JGS4100AAG JGH4100AAG JGC4100AAG JT4100AA
125 100-125 625-1250 JGE4125AAG JGS4125AAG JGH4125AAG JGC4125AAG JT4125AA
160 128-160 800-1600 JGE4160AAG JGS4160AAG JGH4160AAG JGC4160AAG JT4160AA
200 160-200 1000-2000 JGE4200AAG JGS4200AAG JGH4200AAG JGC4200AAG JT4200AA
250 200-250 1250-2500 JGE4250AAG JGS3250AAG JGH4250AAG JGC4250AAG JT4250AA
250 Breaker frame only JGE4250NN JGS4250NN JGH4250NN
250 Moulded case switch JGK7250KSG
13
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Catalogue Numbers, MCCBs with Digitrip 310 Electronic Trip Unit see note 17, 31, 32, 33
Rated Catalogue numbers
current Complete breakers Trip unit External
In, A Protection Type E Type S Type H Type C only neutral CT
3 pole breakers
50 LS JGE305033G JGS305033G JGH305033G JGC305033G JT305033
50 LSI JGE305032G JGS305032G JGH305032G JGC305032G JT305032
50 LSG JGE305035G JGS305035G JGH305035G JGC305035G JT305035 JGFCT050
50 LSIG JGE305036G JGS305036G JGH305036G JGC305036G JT305036 JGFCT050
100 LS JGE310033G JGS310033G JGH310033G JGC310033G JT310033
100 LSI JGE310032G JGS310032G JGH310032G JGC310032G JT310032
100 LSG JGE310035G JGS310035G JGH310035G JGC310035G JT310035 JGFCT100
100 LSIG JGE310036G JGS310036G JGH310036G JGC310036G JT310036 JGFCT100
160 LS JGE316033G JGS316033G JGH316033G JGC316033G JT316033
160 LSI JGE316032G JGS316032G JGH316032G JGC316032G JT316032
160 LSG JGE316035G JGS316035G JGH316035G JGC316035G JT316035 JGFCT160
160 LSIG JGE316036G JGS316036G JGH316036G JGC316036G JT316036 JGFCT160
250 LS JGE325033G JGS325033G JGH325033G JGC325033G JT325033
250 LSI JGE325032G JGS325032G JGH325032G JGC325032G JT325032
250 LSG JGE325035G JGS325035G JGH325035G JGC325035G JT325035 JGFCT250
250 LSIG JGE325036G JGS325036G JGH325036G JGC325036G JT325036 JGFCT250
4 pole breakers
50 LS JGE405033G JGS405033G JGH405033G JGC405033G JT405033 JGFCT050
50 LSI JGE405032G JGS405032G JGH405032G JGC405032G JT405032 JGFCT050
50 LSG JGE405035G JGS405035G JGH405035G JGC405035G JT405035 JGFCT050
50 LSIG JGE405036G JGS405036G JGH405036G JGC405036G JT405036 JGFCT050
100 LS JGE410033G JGS410033G JGH410033G JGC410033G JT410033 JGFCT100
100 LSI JGE410032G JGS410032G JGH410032G JGC410032G JT410032 JGFCT100
100 LSG JGE410035G JGS410035G JGH410035G JGC410035G JT410035 JGFCT100
100 LSIG JGE410036G JGS410036G JGH410036G JGC410036G JT410036 JGFCT100
160 LS JGE416033G JGS416033G JGH416033G JGC416033G JT416033 JGFCT160
160 LSI JGE416032G JGS416032G JGH416032G JGC416032G JT416032 JGFCT160
160 LSG JGE416035G JGS416035G JGH416035G JGC416035G JT416035 JGFCT160
160 LSIG JGE416036G JGS416036G JGH416036G JGC416036G JT416036 JGFCT160
250 LS JGE425033G JGS425033G JGH425033G JGC425033G JT425033 JGFCT250
250 LSI JGE425032G JGS425032G JGH425032G JGC425032G JT425032 JGFCT250
250 LSG JGE425035G JGS425035G JGH425035G JGC425035G JT425035 JGFCT250
250 LSIG JGE425036G JGS425036G JGH425036G JGC425036G JT425036 JGFCT250
Notes
17 M4 hardware is included.
27 For 2 pole applications, use two outer poles. Contact CHS Controls for 2 pole breakers.
28 MCCBs with adjustable thermal trip are not UL/CSA approved.
29 Terminals are not included in breaker frames, must be ordered separately.
30 4 pole thermal magnetic MCCBs have unprotected neutral. Replace the fourth character by ”8” for 0/60% or by ”9” for 0/100% protected neutral.
Example: JGH4250AAG will be JGH8250AAG.
31 Protection type Ir settings
LS Long delay and short delay protection 250 A MCCB 250, 225, 200, 175, 160, 150, 125, 100.
LSI Long delay, short delay and instantaneous protection 160 A MCCB 160, 150, 125, 110, 100, 90, 80, 63.
LSG Long delay, short delay and earth fault protection 100 A MCCB 100, 90, 80, 70, 63, 50, 45, 40.
LSIG Long delay, short delay, instantaneous and earth fault protection 50 A MCCB 50, 45, 40, 32, 30, 25, 20
32 Neutral CT is required for 4-wire systems with protected neutral and for LSG/LSIG trip units. External installation.
33 4 pole electronic trip units MCCBs have unprotected neutral. Replace the fourth character to ”6” for 60% or to ”7” for 100% protected neutral. Protected neutral is not
adjustable. Example: JGH425033G will be JGH725033G.
14
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Earth Leakage Modules for JG Frame MCCBs, bottom mounted
Rated Rated
current voltage Pickup Time Alarm contacts
In, A Un, VAC Poles Standard setting, A Delay, s Earth fault levels Catalogue numbers
150 230-415 3 IEC 0,03-10 Inst.-1 50/100% ELJBE3160W
150 230-415 4 IEC 0,03-10 Inst.-1 50/100% ELJBE4160W
250 230-415 3 IEC 0,03-10 Inst.-1 50/100% ELJBE3250W
250 230-415 4 IEC 0,03-10 Inst.-1 50/100% ELJBE4250W
150 120-480 3 UL/CSA 0,03-10 Inst.-1 50/100% ELJBN3150W
150 120-480 4 UL/CSA 0,03-10 Inst.-1 50/100% ELJBN4150W
250 120-480 3 UL/CSA 0,03-10 Inst.-1 50/100% ELJBN3250W
250 120-480 4 UL/CSA 0,03-10 Inst.-1 50/100% ELJBN4250W
Terminals, Installation Accessories for JG Frame MCCBs see note 20, 34
Description Catalogue numbers
Terminal for Cu cond., pressure type, 250 A, 25-185 mm2/AWG 4-350 T250FJ, included
Terminal for Cu/Al cond., pressure type, 250 A, 25-185 mm2/AWG 4-350 TA250FJ
Terminal for Cu/Al cond., pressure type, 250 A, 25-185 mm2/AWG 4-350 TC250FJ
Endcap kit for busbar/cable lugs, 3 pole, metric hardware FJ3RTWK
Endcap kit for busbar/cable lugs, 4 pole, metric hardware FJ4RTWK
Endcap kit for busbar/cable lugs, 3 pole, imperial hardware FJ3RTDK
Endcap kit for busbar/cable lugs, 4 pole, imperial hardware FJ4RTDK
Multiwire connectors for Cu cond., 250 A, 3 wires, 2,1-13 mm2/AWG 14-6, kit of 3 3TA250J3
Multiwire connectors for Cu cond., 250 A, 6 wires, 2,1-13 mm2/AWG 14-6, kit of 3 3TA250J6
Control wire terminal kit, only for use with T250FJ terminals, 14 pcs per package FJCWTK
Spreader, pole cc=45 mm, 3 pole, hardware not included, use endcap kit FJTEW3
Spreader, pole cc=45 mm, 4 pole, hardware not included, use endcap kit FJTEW4
Terminal shields, ingress protection IP 30, 3 pole FJTS3K
Terminal shields, ingress protection IP 30, 4 pole FJTS4K
Interphase barriers, 6 pcs per package FJIPBK
Interphase barriers, 8 pcs per package FJIPBK4
Plug-in Blocks for JG Frame MCCBs see note 22
Plug-in block for 3 pole breaker, including breaker terminals and trip-on drawout interlock PAD3J
Plug-in block for 4 pole breaker, including breaker terminals and trip-on drawout interlock PAD4J
Notes
20 Multiwire terminals only to be used on 3 pole MCCBs, terminal cover is included.
22 Plug-in block can be installed either on or partly behind mounting plate. Rear terminal stabs are included. Stabs can be converted to front terminals.
23 See page 7 for possible installation combinations.
24 Rotary through-the-door handle, see page 24 for min and max enclosure depth.
25 Flexshaft mechanism, additional hardware may be required depending on enclosure type. Contact CHS Controls for more information.
26 Contact CHS Controls for breaker interlock kits and cylinder locks.
34 Terminal T250FJ is made of stainless steel. Terminal TA250FJ is made of aluminium. Terminal TC250FJ is made of copper.
test
reset
WAR NIN G
T250FJ TA250FJ FJCWTK
TC250FJ
Multiwire terminal Endcap kit
Spreader Interphase barrier
Terminal shield
15
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Internal Accessories for JG Frame MCCBs see note 23
Description Catalogue Number
Auxiliary contact, 1 change-over contact AUX1A1BPK
Auxiliary contact, 2 change-over contacts AUX2A2BPK
Alarm contact, 1 change-over contact ALM1M1BJPK
Alarm contact, 2 change-over contacts ALM2M2BJPK
Combination auxiliary and alarm contact, 1 change-over contact of each AUXALRMJPK
Shunt trip, 120 VAC SNT120CPK
Shunt trip, 240 VAC SNT1200PK
Shunt trip, 380-600 VAC SNT480APK
Shunt trip, 24-48 VDC SNT060CPK
Undervoltage release, 120 VAC UVR120APK
Undervoltage release, 208-240 VAC, 380-500 VAC UVR480APK
Undervoltage release, 525-600 VAC UVR600APK
Undervoltage release, 24 VAC/VDC UVR024CPK
Undervoltage release, 48 VAC UVR048APK
Undervoltage release, 48 VDC UVR048DPK
Undervoltage release, 120 VDC UVR125DPK
External Accessories for JG Frame MCCBs see note 24, 25, 26
Direct (close-coupled) rotary handle JHMCCB
Direct (close-coupled) rotary handle with door interlock JHMCCBI
Rotary through-the-door handle, black - IP 54/NEMA 12, 152 mm shaft FJHMVD06B
Rotary through-the-door handle, black - IP 54/NEMA 12, 304 mm shaft FJHMVD12B
Rotary through-the-door handle, black - IP 54/NEMA 12, 609 mm shaft FJHMVD24B
Rotary through-the-door handle, red - IP 54/NEMA 12, 152 mm shaft FJHMVD06R
Rotary through-the-door handle, red - IP 54/NEMA 12, 304 mm shaft FJHMVD12R
Rotary through-the-door handle, red - IP 54/NEMA 12, 609 mm shaft FJHMVD24R
Rotary through-the-door handle, black - IP 65/NEMA 4X, 152 mm shaft FJHMVD06BX
Rotary through-the-door handle, black - IP 65/NEMA 4X, 304 mm shaft FJHMVD12BX
Rotary through-the-door handle, black - IP 65/NEMA 4X, 609 mm shaft FJHMVD24BX
Rotary through-the-door handle, red - IP 65/NEMA 4X, 152 mm shaft FJHMVD06RX
Rotary through-the-door handle, red - IP 65/NEMA 4X, 304 mm shaft FJHMVD12RX
Rotary through-the-door handle, red - IP 65/NEMA 4X, 609 mm shaft FJHMVD24RX
Flexshaft mechanism, fl ange mounted handle - IP 54/NEMA 12, 1,2 m wire JHMFS04
Flexshaft mechanism, fl ange mounted handle - IP 54/NEMA 12, 2,1 m wire JMHFS07
Flexshaft mechanism, fl ange mounted handle - IP 65/NEMA 4X, 1,2 m wire JHMFS04X
Flexshaft mechanism, fl ange mounted handle - IP 65/NEMA 4X, 2,1 m wire JHMFS07X
Motor operator, 120 VAC EOPFJ240C
Motor operator, 240 VAC EOPFJ240C
Motor operator, 24 VDC EOPFJ24D
Motor operator, 48 VDC EOPFJ48D
Motor operator, 120 VDC EOPFJ240C
Handle block for temporary use, padlockable in On/Off position FJPHB
Handle block for temporary use, padlockable in Off position FJPHBOFF
Handle block, fi xed mounted on breaker, padlockable in On/Off position FJPHL
Handle block, fi xed mounted on breaker, padlockable in Off position FJPHLOFF
Plug-in test kit for electronic trip units, 120 VAC power supply MTST120V
Plug-in test kit for electronic trip units, 230 VAC power supply MTST230V
Discrimination/system design software on CD Contact CHS Controls
ON/I
T
rip
OFF/O
ON/I
T
rip
OFF/O
ON
OFF
ON
OFF
O
I
Handle block Handle block
xed mounted temporary use
Flexshaft mechanism, fl ange mounted
Motor operator
Rotary through-the-door handle
Direct rotary handle
Undervoltage release
Shunt trip
Aux/alarm switch
16
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Moulded Case Circuit Breakers for Plant Protection, LG Frame 250 - 630 A, IEC/UL/CSA
Breaker Capacity
Breaking capacity , kA, VAC
Breaker Rated voltage, Ue, VAC IEC 60947-2, Icu/Ics UL 489/CSA
type IEC UL/CSA 230 400 690 240 480 600
E 690 600 65/65 35/35 12/6 65 35 18
S 690 600 85/85 50/50 20/10 85 50 25
H 690 600 100/100 70/70 25/13 100 65 35
C 690 600 200/150 100/75 35/18 200 100 50
Catalogue Numbers, MCCBs with Thermal-Magnetic Trip Unit see note 29, 35, 36
Rated Adjustable range Catalogue numbers
current Thermal Magnetic Complete breakers Trip unit
In, A Ir, A Im, A Type E Type S Type H Type C only
3 pole breakers
250 Fixed 1250-2500 LGE3250FAG LGS3250FAG LGH3250FAG LGC3250FAG LT3250FA
300 Fixed 1500-3000 LGE3300FAG LGS3300FAG LGH3300FAG LGC3300FAG LT3300FA
350 Fixed 1750-3500 LGE3350FAG LGS3350FAG LGH3350FAG LGC3350FAG LT3350FA
400 Fixed 2000-4000 LGE3400FAG LGS3400FAG LGH3400FAG LGC3400FAG LT3400FA
500 Fixed 2500-5000 LGE3500FAG LGS3500FAG LGH3500FAG LGC3500FAG LT3500FA
600 Fixed 3000-6000 LGE3600FAG LGS3600FAG LGH3600FAG LGC3600FAG LT3600FA
250 200-250 1250-2500 LGE3250AAG LGS3250AAG LGH3250AAG LGC3250AAG LT3250AA
320 256-320 1600-3200 LGE3320AAG LGS3320AAG LGH3320AAG LGC3320AAG LT3320AA
400 320-400 2000-4000 LGE3400AAG LGS3400AAF LGH3400AAG LGC3400AAG LT3400AA
500 400-500 2500-5000 LGE3500AAF LGS3500AAG LGH3500AAG LGC3500AAG LT3500AA
630 504-630 3150-6300 LGE3630AAG LGS3630AAG LGH3630AAG LGC3630AAG LT3630AA
630 Breaker frame only LGE3630NN LGS3630NN LGH3630NN LGC3630NN
400 Moulded case switch LGK3400KSG
630 Moulded case switch LGK3630KSG
4 pole breakers
250 Fixed 1250-2500 LGE4250FAG LGS4250FAG LGH4250FAG LGC4250FAG LT4250FA
300 Fixed 1500-3000 LGE4300FAG LGS4300FAG LGH4300FAG LGC4300FAG LT4300FA
350 Fixed 1750-3500 LGE4350FAG LGS4350FAG LGH4350FAG LGC4350FAG LT4350FA
400 Fixed 2000-4000 LGE4400FAG LGS4400FAG LGH4400FAG LGC4400FAG LT4400FA
500 Fixed 2500-5000 LGE4500FAG LGS4500FAG LGH4500FAG LGC4500FAG LT4500FA
600 Fixed 3000-6000 LGE4600FAG LGS4600FAG LGH4600FAG LGC4600FAG LT4600FA
250 200-250 1250-2500 LGE4250AAG LGS4250AAG LGH4250AAG LGC4250AAG LT4250AA
320 256-320 1600-3200 LGE4320AAG LGS4320AAG LGH4320AAG LGC4320AAG LT4320AA
400 320-400 2000-4000 LGE4400AAG LGS4400AAG LGH4400AAG LGC4400AAG LT4400AA
500 400-500 2500-5000 LGE4500AAG LGS4500AAG LGH4500AAG LGC4500AAG LT4500AA
630 504-630 3150-6300 LGE4630AAG LGS4630AAG LGH4630AAG LGC4630AAG LT4630AA
630 Breaker frame only LGE4630NN LGS4630NN LGH4630NN LGC4630NN
400 Moulded case switch LGK4400KSG
630 Moulded case switch LGK4630KSG
17
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Catalogue Numbers, MCCBs with Digitrip 310 Electronic Trip Unit see note 35, 36, 38, 39
Rated Catalogue numbers
current Complete breakers Trip unit External
In, A Protection Type E Type S Type H Type C only neutral CT
3 pole breakers
250 LS LGE325033G LGS325033G LGH325033G LGC325033G LT325033
250 LSI LGE325032G LGS325032G LGH325032G LGC325032G LT325032
250 LSG LGE325035G LGS325035G LGH325035G LGC325035G LT325035 LGFCT250
250 LSIG LGE325036G LGS325036G LGH325036G LGC325036G LT325036 LGFCT250
400 LS LGE340033G LGS340033G LGH340033G LGC340033G LT340033
400 LSI LGE340032G LGS340032G LGH340032G LGC340032G LT340032
400 LSG LGE340035G LGS340035G LGH340035G LGC340035G LT340035 LGFCT400
400 LSIG LGE340036G LGS340036G LGH340036G LGC340036G LT340036 LGFCT400
600 LS LGE360033G LGS360033G LGH360033G LGC360033G LT360033
600 LSI LGE360032G LGS360032G LGH360032G LGC360032G LT360032
600 LSG LGE360035G LGS360035G LGH360035G LGC360035G LT360035 LGFCT600
600 LSIG LGE360036G LGS360036G LGH360036G LGC360036G LT360036 LGFCT600
630 LS LGE363033G LGS363033G LGH363033G LGC363033G LT363033
630 LSI LGE363032G LGS363032G LGH363032G LGC363032G LT363032
630 LSG LGE363035G LGS363035G LGH363035G LGC363035G LT363035 LGFCT630
630 LSIG LGE363036G LGS363036G LGH363036G LGC363036G LT363036 LGFCT630
4 pole breakers
250 LS LGE425033G LGS425033G LGH425033G LGC425033G LT425033 LGFCT250
250 LSI LGE425032G LGS425032G LGH425032G LGC425032G LT425032 LGFCT250
250 LSG LGE425035G LGS425035G LGH425035G LGC425035G LT425035 LGFCT250
250 LSIG LGE425036G LGS425036G LGH425036G LGC425036G LT425036 LGFCT250
400 LS LGE440033G LGS440033G LGH440033G LGC440033G LT440033 LGFCT400
400 LSI LGE440032G LGS440032G LGH440032G LGC440032G LT440032 LGFCT400
400 LSG LGE440035G LGS440035G LGH440035G LGC440035G LT440035 LGFCT400
400 LSIG LGE440036G LGS440036G LGH440036G LGC440036G LT440036 LGFCT400
600 LS LGE460033G LGS460033G LGH460033G LGC460033G LT460033 LGFCT600
600 LSI LGE460032G LGS460032G LGH460032G LGC460032G LT460032 LGFCT600
600 LSG LGE460035G LGS460035G LGH460035G LGC460035G LT460035 LGFCT600
600 LSIG LGE460036G LGS460036G LGH460036G LGC460036G LT460036 LGFCT600
630 LS LGE463033G LGS463033G LGH463033G LGC463033G LT463033 LGFCT630
630 LSI LGE463032G LGS463032G LGH463032G LGC463032G LT463032 LGFCT630
630 LSG LGE463035G LGS463035G LGH463035G LGC463035G LT463035 LGFCT630
630 LSIG LGE463036G LGS463036G LGH463036G LGC463036G LT463036 LGFCT630
Notes
29 Terminals are not included in breaker frames, must be ordered separately.
32 Neutral CT is required for 4-wire systems with protected neutral and for LSG/LSIG trip units. External installation.
35 M5 hardware is included.
36 630 A MCCBs as well as MCCBs with adjustable thermal trip are not UL/CSA approved.
37 4 pole thermal magnetic MCCBs have unprotected neutral. Replace the fourth character by ”7” for 100%, by ”8” for 0-60% or by9” for 0-100% protected neutral.
Example: LGH4630AAG will be LGH7630AAG.
38 Protection type Ir settings
LS Long delay and short delay protection 630 A MCCB 630, 600, 500, 400, 350, 315, 300, 250.
LSI Long delay, short delay and instantaneous protection 600 A MCCB 600, 500, 450, 400, 350, 315, 300, 250.
LSG Long delay, short delay and earth fault protection 400 A MCCB 400, 350, 315, 300, 300, 250, 225, 200, 160.
LSIG Long delay, short delay, instantaneous and earth fault protection 250 A MCCB 250,225, 200, 175, 160, 150, 125, 100.
39 4 pole electronic trip units MCCBs have unprotected neutral. Replace the fourth character by ”6” for 60% or by ”7” for 100% protected neutral. Protected neutral is not
adjustable. Example: LGH463033G will be LGH763033G.
18
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Earth Leakage Modules for LG Frame MCCBs, bottom mounted
Rated Rated
current voltage Pickup Time Alarm contacts
In, A Un, VAC Poles Standard setting, A Delay, s Earth fault levels Catalogue numbers
400 230-415 3 IEC 0,03-10 Inst.-1 50/100% ELLBE3400W
400 230-415 4 IEC 0,03-10 Inst.-1 50/100% ELLBE4400W
630 230-415 3 IEC 0,03-10 Inst.-1 50/100% ELLBE3630W
630 230-415 4 IEC 0,03-10 Inst.-1 50/100% ELLBE4630W
400 120-480 3 UL/CSA 0,03-10 Inst.-1 50/100% ELLBN3400W
400 120-480 4 UL/CSA 0,03-10 Inst.-1 50/100% ELLBN4400W
600 120-480 3 UL/CSA 0,03-10 Inst.-1 50/100% ELLBN3600W
600 120-480 4 UL/CSA 0,03-10 Inst.-1 50/100% ELLBN4600W
Terminals, Installation Accessories for LG Frame MCCBs see note 40, 41
Description Catalogue numbers
Terminal for Cu/Al cond., pressure type, 400 A, 35-240 mm2/AWG 2-500 TA350LK, included
Terminal for Cu cond., pressure type, 400 A, 35-240 mm2/AWG 2-500 T350LK
Terminals for Cu/Al cond., pressure type, 400 A, 240-380 mm2/kcmil 500-750, kit of 3 3TA631LK
Terminals for Cu cond., pressure type, 400 A, 240-380 mm2/kcmil 500-750, kit of 3 3T631LK
Terminals for Cu/Al cond., pressure type, 400 A, 240-380 mm2/kcmil 500-750, kit of 4 4TA631LK
Terminals for Cu cond., pressure type, 400 A, 240-380 mm2/kcmil 500-750, kit of 4 4T631LK
Terminals for Cu/Al cond., pressure type, 630 A, 2*35-240 mm2/AWG 2*2-500, kit of 3 3TA632LK, included
Terminals for Cu cond., pressure type, 630 A, 2*35-240 mm2/AWG 2*2-500, kit of 3 3T632LK
Terminals for Cu/Al cond., pressure type, 630 A, 2*35-240 mm2/AWG 2*2-500, kit of 4 4TA632LK, included
Terminals for Cu cond., pressure type, 630 A, 2*35-240 mm2/AWG 2*2-500, kit of 4 4T632LK
Endcap kit for busbar/cable lugs, 3 pole, metric hardware L3RTWK
Endcap kit for busbar/cable lugs, 4 pole, metric hardware L4RTWK
Endcap kit for busbar/cable lugs, 3 pole, imperial hardware L3RTDK
Endcap kit for busbar/cable lugs, 4 pole, imperial hardware L4RTDK
Spreader, pole cc=54 mm, 3 pole, hardware not included, use endcap kit LGTEW3
Spreader, pole cc=54 mm, 4 pole, hardware not included, use endcap kit LGTEW4
Terminal shields, ingress protection IP 30, 3 pole LTS3K
Terminal shields, ingress protection IP 30, 4 pole LTS4K
Interphase barriers, 2 pcs per package IPB3
Plug-in Blocks for LG Frame MCCBs see note 22
Plug-in block for 3 pole breaker, including breaker terminals and trip-on drawout interlock PAD3L
Plug-in block for 4 pole breaker, including breaker terminals and trip-on drawout interlock PAD4L
Notes
22 Plug-in block can be installed either on or partly behind mounting plate. Rear terminal stabs are included. Stabs can be converted to front terminals.
23 See page 7 for possible installation combinations.
24 Rotary through-the-door handle, see page 24 for min and max enclosure depth.
25 Flexshaft mechanism, additional hardware may be required depending on enclosure type. Contact CHS Controls for more information.
26 Contact CHS Controls for breaker interlock kits and cylinder locks.
40 Terminal cover is included for terminals 3TA631LK, 3T631LK, 4TA631LK, 4T631LK, 3TA632LK, 3T632LK, 4TA632LK and 4T632LK.
41 Terminals TA350LK, 3TA631LK, 4TA631LK, 3TA632LK and 4TA632LK are made of aluminium. Terminals T350LK, 3T631LK, 4T631LK, 3T632LK and 4T632LK are
made of copper.
test
reset
WAR NIN G
TA632LK TA631LK TA350LK
T632LK T631LK T350LK
Endcap kit
Spreader Interphase barrier
Terminal shield
19
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Internal Accessories for LG Frame MCCBs see note 23
Description Catalogue Number
Auxiliary contact, 1 change-over contact AUX1A1BPK
Auxiliary contact, 2 change-over contacts AUX2A2BPK
Alarm contact, 1 change-over contact ALM1M1BJPK
Alarm contact, 2 change-over contacts ALM2M2BJPK
Combination auxiliary and alarm contact, 1 change-over contact of each AUXALRMJPK
Shunt trip, 120 VAC SNT120CPK
Shunt trip, 240 VAC SNT1200PK
Shunt trip, 380-600 VAC SNT480APK
Shunt trip, 24-48 VDC SNT060CPK
Undervoltage release, 120 VAC UVR120APK
Undervoltage release, 208-240 VAC, 380-500 VAC UVR480APK
Undervoltage release, 525-600 VAC UVR600APK
Undervoltage release, 24 VAC/VDC UVR024CPK
Undervoltage release, 48 VAC UVR048APK
Undervoltage release, 48 VDC UVR048DPK
Undervoltage release, 120 VDC UVR125DPK
External Accessories for LG Frame MCCBs see note 24, 25, 26
Direct (close-coupled) rotary handle LHMCCB
Direct (close-coupled) rotary handle with door interlock LHMCCBI
Rotary through-the-door handle, black - IP 54/NEMA 12, 152 mm shaft KLHMVD06B
Rotary through-the-door handle, black - IP 54/NEMA 12, 304 mm shaft KLHMVD12B
Rotary through-the-door handle, black - IP 54/NEMA 12, 609 mm shaft KLHMVD24B
Rotary through-the-door handle, red - IP 54/NEMA 12, 152 mm shaft KLHMVD06R
Rotary through-the-door handle, red - IP 54/NEMA 12, 304 mm shaft KLHMVD12R
Rotary through-the-door handle, red - IP 54/NEMA 12, 609 mm shaft KLHMVD24R
Rotary through-the-door handle, black - IP 65/NEMA 4X, 152 mm shaft KLHMVD06BX
Rotary through-the-door handle, black - IP 65/NEMA 4X, 304 mm shaft KLHMVD12BX
Rotary through-the-door handle, black - IP 65/NEMA 4X, 609 mm shaft KLHMVD24BX
Rotary through-the-door handle, red - IP 65/NEMA 4X, 152 mm shaft KLHMVD06RX
Rotary through-the-door handle, red - IP 65/NEMA 4X, 304 mm shaft KLHMVD12RX
Rotary through-the-door handle, red - IP 65/NEMA 4X, 609 mm shaft KLHMVD24RX
Flexshaft mechanism, fl ange mounted handle - IP 54/NEMA 12, 1,2 m wire LHMFS04
Flexshaft mechanism, fl ange mounted handle - IP 54/NEMA 12, 2,1 m wire LMHFS07
Flexshaft mechanism, fl ange mounted handle - IP 65/NEMA 4X, 1,2 m wire LMHFS04X
Flexshaft mechanism, fl ange mounted handle - IP 65/NEMA 4X, 2,1 m wire LMHFS07X
Motor operator, 120 VAC EOPLG240C
Motor operator, 240 VAC EOPLG240C
Motor operator, 24 VDC EOPLG24D
Motor operator, 48 VDC EOPLG48D
Motor operator, 120 VDC EOPLG240C
Handle block for temporary use, padlockable in On/Off position LBHP
Handle block for temporary use, padlockable in Off position LBHPOFF
Handle block, fi xed mounted on breaker, padlockable in On/Off position LPHL
Handle block, fi xed mounted on breaker, padlockable in Off position LPHLOFF
Plug-in test kit for electronic trip units, 120 VAC power supply MTST120V
Plug-in test kit for electronic trip units, 230 VAC power supply MTST230V
Discrimination/system design software on CD Contact CHS Controls
ON/I
T
rip
OFF/O
ON/I
T
rip
OFF/O
ON
OFF
ON
OFF
O
I
Handle block Handle block
xed mounted temporary use
Flexshaft mechanism, fl ange mounted
Motor operator
Direct rotary handle
Rotary through-the-door handle
Undervoltage release
Shunt trip
Aux/alarm switch
20
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Moulded Case Circuit Breakers for Motor Starters EG - LG Frame 3 - 600 A, IEC/UL/CSA
Combination Ratings see note 42
Combination ratings with
Eaton’s Cutler-Hammer starters, kA, VAC
Breaker Rated voltage, Ue, VAC IEC 60947-4-1 UL 489/CSA
frame IEC UL/CSA 230 400 240 480 600
EG 690 600Y/347 100/65 100/65 100 100 25
JG 690 600 65 65 100 100 25
LG 690 600 65 65 100 100 25
Catalogue Numbers, 3 Pole MCCBs with Magnetic Trip Unit for Starter Combinations see note 43, 44, 45, 46
Rated Adjustable settings Catalogue numbers
current Magnetic Complete circuit breakers
In, A Im, A EG Frame JG Frame LG Frame
3 9, 15, 21, 27, 30, 33 HMCPE003A0C
7 21, 35, 49, 63, 70, 77 HMCPE007C0C
15 45, 75, 105, 135, 150, 165 HMCPE015E0C
30 90, 150, 210, 270, 300, 330 HMCPE030H1C
50 150, 250, 350, 450, 500 ,550 HMCPE050K2C
70 210, 350 ,490, 630, 700, 770 HMCPE070M2C
100 300, 500, 700, 900, 1000, 1100 HMCPE100R3C
100 500, 750, 1000, 1250, 1375, 1500 HMCPE100T3C
250 500-1000 HMCPJ250D5L
250 625-1250 HMCPJ250F5L
250 750-1500 HMCPJ250G5L
250 875-1750 HMCPJ250J5L
250 1000-2000 HMCPJ250K5L
250 1125-2250 HMCPJ250L5L
250 1250-2500 HMCPJ250W5L
600 1125-2250 HMCPL600L
600 1500-3000 HMCPL600N
600 1750-3500 HMCPL600R
600 2000-4000 HMCPL600X
600 2250-4500 HMCPL600Y
600 2500-5000 HMCPL600P
600 3000-6000 HMCPL600M
Notes
42 Combination ratings per IEC 60947-4-1, Type 2 coordination, are based on combination use with Eaton’s Cutler-Hammer IT Starters.
The UL/CSA approval is based on combination use with Eaton’s Cutler-Hammer IT and Freedom Series starters. Contact CHS Controls for coordination information.
43 The MCCBs can be used for DC applications, max 250 VDC.
44 Trip levels for DC applications, actual trip level is approximately 40% higher than values shown.
45 Contact CHS Controls for MCCBs for thermal magnetic motor protection MCCBs according to IEC 60947-4.
46 For accessories see page 10 for EG frame, 14 for JG frame and page 18 for LG frame.
21
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Dimensions, Moulded Case Circuit Breakers, mm see note 47, 48
Notes
47 EG frame mounted on DIN rail increases depth with 9 mm.
48 Terminal shields on EG frame add 46 mm to line/load side, terminal shields on JG frame add 48 mm to line/load side and terminal shields on LG frame add 54 mm
to line/load side.
105
35,5 cc poles
140 9023
25,4 cc poles 25,4 cc poles
140
35,5 cc poles
43,5 cc poles 43,5 cc poles
7614
139 183 10927
102
76
140 140
178 178 178
257257257
EG Frame, 3 pole, Front View EG Frame, 4 pole, Front View EG Frame, Side View
JG Frame, 3 pole, Front View JG Frame, 4 pole Front View JG Frame, Side View
LG Frame, 3 pole, Front View LG Frame, 4 pole Front View LG Frame, Side View
22
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Dimensions, MCCBs with Earth Leakage Protection Modules, mm see note 47, 48, 49
105
286
35,5 cc poles
140
286 286
9023
178
25,4 cc poles 25,4 cc poles
204
140
35,5 cc poles
43,5 cc poles 43,5 cc poles
76
14
140
140
390390390
139 183 111
27
EG Frame, 3 pole, Front View EG Frame, 4 pole, Front View EG Frame, Side View
JG Frame, 3 pole, Front View JG Frame, 4 pole, Front View JG Frame, Side View
LG Frame, 3 pole, Front View LG Frame, 4 pole, Front View LG Frame, Side View
23
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Dimensions, Moulded Case Circuit Breaker Plug-In Blocks, mm see note 50
Notes
47 EG frame mounted on DIN rail increases depth with 9 mm.
48 Terminal shields on EG frame add 46 mm to line/load side, terminal shields on JG frame add 48 mm to line/load side and terminal shields on LG frame add 54 mm
to line/load side.
49 Earth leakage protection module for EG frame, interconnection cables are included. Load terminals are located at the bottom of earth leakage protection module.
50 Plug-in block can be installed partly behind mounting plate (as illustrated) or on mounting plate. Stabs can be converted to front terminals, contact CHS Controls for
dimensions.
10927
90
4
172
76 60
14
14
15
65
120
25,4
103
120
65
15
25,4
78
123
5
220
15
90
140
35
142
9023
15
140
90
35
107
170
10
310
121
181
15
44
186
44
142
15
121
181
70
90
EG Frame, 3 pole Bottom View EG Frame, 4 pole Bottom View EG Frame, Side View
JG Frame, 3 pole Bottom View JG Frame, 4 pole Bottom View JG Frame, Side View
LG Frame, 3 pole Bottom View LG Frame, 4 pole Bottom View LG Frame, Side View
CHS Controls AB
Florettgatan 33
SE-254 67 Helsingborg, Sweden
Phone +46 42 386100, fax +46 42 386129
chs@chscontrols.se
www.chscontrols.se
Catalogue PM1043E April 2005
A
l
l
t
i
d
t
i
l
l
g
ä
n
g
l
i
g
-
A
l
lt
i
d
ö
p
p
e
n
!
A
l
w
a
y
s
a
v
a
i
l
a
b
l
e
-
A
l
w
a
y
s
o
p
e
n
!
www.chscontrols.se
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
Dimensions, Moulded Case Circuit Breakers with Rotary Handle Mechanisms, mm
131
152 mm shaft: Max 245
305 mm shaft: Max 398
610 mm shaft: Max 703
50
171
152 mm shaft: Max 276
305 mm shaft: Max 400
610 mm shaft: Max 734
50
20850
152 mm shaft: Max 314
305 mm shaft: Max 467
610 mm shaft: Max 772
EG Frame, Rotary Through-the-Door handle EG Frame, Direct Rotary Handle
LG Frame, Rotary Through-the-Door handle LG Frame, Direct Rotary Handle
JG Frame, Rotary Through-the-Door handle JG Frame, Direct Rotary Handle