2Specifications are subject to change without notice (25.10.99)
A 108, A 101, A 208, A 201
A 108, A 101 A 208, A 201
Output SPDT relay DPDT relay
Basic electrical insulation 250 VAC (rms) (contact/electronics) 250 VAC (rms) (contacts/elec., contact/contact)
Contact ratings (Ag-CdO) µ (micro gap) µ (micro gap)
Resistive loads AC 1 10 A/250 VAC (2500 VA) 8 A/250 VAC (2000 VA)
DC 1 1 A/250 VDC (250 W) 0.4 A/250 VDC (100 W)
or 10 A/25 VDC (250 W) 4 A/25 VDC (100 W)
Small inductive loads AC 15 2.5 A/230 VAC 2.5 A/230 VAC
DC 13 5 A/24 VDC 5 A/24 VDC
Mechanical life ≥30 x 106operations ≥30 x 106operations
Electrical life AC 1 ≥2.5 x 105operations (at max. load) ≥2.5 x 105operations (at max. load)
Operating frequency ≤7200 operations/h ≤7200 operations/h
Insulation voltages
Rated insulation voltage ≥2.0 kVAC (rms) (contact/electronics) ≥2.0 kVAC (rms) (contact/electronics)
Rated transient protection volt.
4 kV (1.2/50 µs) (contact/electronics) (IEC 60664) 4 kV (1.2/50 µs) (contact/electronics) (IEC 60664)
Power supply
A 101, A 201
Power-on delay ≤200 ms
Power-off delay ≥250 ms
Indication for
Output ON LED, red
Environment IP 20 B
Polution degree 2 (IEC 60664)
Operating temperature -20° to +50°C (-4° to +122°F)
Storage temperature -50° to +85°C (-58° to +185°F)
Weight 85 g
Approvals UL, CSA
Power supply AC types installation cat. III (IEC 60664)
Rated operational voltage
through pins 2 & 10 220 220 VAC + 15/- 20%,
or pins 2 & 7 45 to 65 Hz
120 120 VAC + 15/- 20%,
45 to 65 Hz
024 24 VAC + 15/- 20%,
45 to 65 Hz
Drop out tolerance ≥10 ms
Rated insulation voltage None
Rated transient protection volt. 4 kV (1.2/50 µs) @ 220 VAC
2.5 kV (1.2/50 µs) @ 120 VAC
800 V (1.2/50 µs) @ 24 VAC
(line/neutral)
Power supply DC type Installation cat. III (IEC 60664)
Rated operational voltage 024 24 VDC + 15/- 20% (pin 2 pos.)
Rated insulation voltage None
Rated transient protection volt. 800 V (1.2/50 µs)
Consumption AC supply 60 mA @ 50 Hz/70 mA @ 60 Hz
DC supply 1 W
Mode of Operation
The delay period begins when
power supply is applied.
At the end of the set delay,
the relay will operate and will
not release until power sup-
ply is interrupted.
A recovery period of 250 ms
should be allowed before re-
applying power supply.
If power supply is interrupted
for more than 250 ms before
the relay operates, the time
circuit is reset to zero and the
time relay is ready for a new
time period.
Wiring Diagrams
Output Specifications
Supply Specifications General Specifications
Power supply
A 108, A 208