date 01/17/2013 │ page 2 of 7CUI Inc │ SERIES: VDRS-150 │ DESCRIPTION: AC-DC DIN RAIL
INPUT
parameter conditions/description min typ max units
voltage 88
124
264
373
Vac
Vdc
frequency 47 63 Hz
current at 115 Vac
at 230 Vac
2.6
1.3
A
A
inrush current at 115 Vac
at 230 Vac
33
65
A
A
power factor correction at 230 Vac
at 115 Vac
0.90
0.98
leakage current at 240 Vac 1mA
OUTPUT
parameter conditions/description min typ max units
voltage accuracy ±1 %
line regulation ±0.5 %
load regulation 5±1%
temperature coeffi cient (0 ~ 50°C) ±0.03 %/°C
hold-up time at 115 / 230 Vac, cold start 16 ms
voltage adjustment range -2 +8 %
Note: 1. All specifi cation are measured at 230 Vac input, rated load, 25°C unless otherwise specifi ed.
PROTECTIONS
parameter conditions/description min typ max units
over voltage protection
latch-off mode, restart
to recover from fault
24 V model
48 V model
120
117
138
135
%
%
Kicks in between 105~150% rated output power
when the fault persist for about 3 sec, then clamps
output voltage down, automatic recovery’ >150%
rated power or short circuit would cause the power
supply to go in to constant current limiting; if fault
condition is not removed after 5 times, then the
converter will shutdown and need to be restarted
to recover from fault.
over load protection constant current limiting, automatically recovers
after fault condition is removed 105 150 %
over temperature protection output shut down and auto restart upon reduction
of temperature 90 95 100 °C
DC ok relay contact ratings at 0.3 A
at 1 A and 0.5 A
60
30
Vdc
Vdc