Recycling (Pulse Generator) HRDR Power-Time Time Delay Relay Description The HRDR Series combines an electromechanical relay and microcontroller timing circuitry. It offers 12 to 230 V operation in five ranges and factory fixed, onboard or externally adjustable time delays with a repeat accuracy of +/-0.5%. The high switching capacity of the output contacts allow for direct control of heavy loads like compressors, pumps, motors, heaters, and lighting. Bypass/reset switch option allows operator to interrupt normal recycling sequence and energize output relay. An excellent choice for OEM applications. Operation 30 A SPDT N.O. Output Contacts 12 ... 230 V Operation in 5 Ranges Encapsulated Circuitry Delays from 100 ms ... 1000 m in 6 Ranges Independent Adjustment of ON and OFF Delays +/-0.5% Repeat Accuracy +/-5% Factory Calibration Fixed or Onboard or External Adjustment Function Upon application of input voltage, the ON time T1 begins and output relay energizes. At the end of the ON time, the output relay de-energizes and the OFF time T2 begins. At the end of the OFF time, the output relay energizes and the cycle repeats as long as input voltage is applied. Some recycling timers have the OFF time as the first delay. Reset: Removing input voltage resets output and time delays, and returns sequence to the first delay. Bypass/Reset Switch: Closing the normally open bypass/reset switch energizes the output relay and resets the time delays. Opening the switch restarts recycling operation with the first delay. Connection Recycling w/Reset Switch V = Voltage S1 = Reset Switch L = Load R = Reset T1 = ON Time T2 = OFF Time = Undefined time Mechanical View Approvals: Inches (Millimeters) Note: Terminals 4 & 5 and/or 7 & 8 are only included on externally adjustable units. NO = Normally Open S1 = Reset Switch C = Common, Transfer Contact L = Load Relay contacts are non-isolated. RT is included when external adjustment is ordered. Dashed lines are internal connections. Terminal 6 is included when Bypass/Reset is selected. X X Input - 1 - 12 V DC - 2 - 24 V AC - 3 - 24 V DC - 4 - 120 V AC - 6 - 230 V AC External Adjust - 1 - Both Times Fixed - 2 - Both Times Onboard Adj. - 3 - Both Times External Adj. - 4 - ON Time External Adj. OFF Time Fixed - 5 - ON Time Fixed OFF Time External Adj. - 6 - ON Time Onboard Adj. OFF Time, Fixed - 7 - ON Time, Fixed OFF Time Onboard Adj. - 8 - ON Time Onboard Adj. OFF Time, External Adj. - 9 - ON Time, External Adj. OFF Time Onboard Adj. Example P/N: HRDR431A4R Fixed - HRDR410.2SB100S 5.168 X T1 ON Time * - 0 - 0.1 ... 10 s - 1 - 1 ... 100 s - 2 - 10 ... 1000 s - 3 - 0.1 ... 10 m - 4 - 1 ... 100 m - 5 - 10... 1000 m X X X Operating Sequence - A - ON Time First - B - OFF Time First T2 OFF Time * - 0 - 0.1 ... 10 s - 1 - 1 ... 100 s - 2 - 10 ... 1000 s - 3 - 0.1 ... 10 m - 4 - 1 ... 100 m - 5 - 10 ...1000 m Operation Blank - No Bypass/ Reset Option - R - Bypass/Reset Option * If Fixed Delay is selected, insert delay [ 0.1 ... 1000 ] followed by ( S ) sec. or [ 0.1 ... 1000 ] ( M ) min. HRDRGen HRDR Series 10.03.05 Ordering Table Low Voltage Products & Systems Recycling (Pulse Generator) HRDR Power-Time Time Delay Relay Technical Data Time Delay Range Repeat Accuracy Tolerance (Factory Calibration) Reset Time Time Delay vs. Temperature & Voltage Input Voltage Tolerance 12 V DC & 24 V DC 24 ... 230 V AC Line Frequency Power Consumption Output Type Form Ratings: General Purpose 125/240 V AC Resistive 125/240 V AC 28 V DC Motor Load 125 V AC 240 V AC Life Protection Surge Circuitry Dielectric Breakdown Insulation Resistance Polarity Mechanical Mounting Package Termination Environmental Operating/Storage Temperature Humidity Weight External Resistance vs Time Delay 100 ms ... 1000 m in 6 adjustable ranges or fixed +/-0.5% or 20 ms, whichever is greater +/-5% 150 ms +/-2% 12 or 24 V DC; 24, 120, or 230 V AC -15% ... +20% -20% ... +10% 50 ... 60 Hz AC 4 VA; DC 2 W Electromechanical relay SPDT, non-isolated SPDT- N.O. SPDT-N.C. 30 A 15 A 30 A 15 A 20 A 10 A 1 hp* 1/4 hp** 2 hp** 1 hp** Mechanical -- 1 x 106; Electrical -- 1 x 105, *3 x 104, **6,000 IEEE C62.41-1991 Level A Encapsulated 2000 V RMS terminals to mounting surface 100 M DC units are reverse polarity protected Surface mount with one #10 (M5 x 0.8) screw 3 x 2 x 1.5 in. (76.7 x 51.3 x 38.1mm) 0.25 in. (6.35 mm) male quick connect terminals -40C ... +60C/-40C ... +85C 95% relative non-condensing 3.9 oz (111 g) Accessories Versa-knob P/N: P0700-7 B A External adjust potentiometer P/Ns: P1004-95 ( fig. A) P1004-95-X (fig. B) Female quick connect P/Ns: P1015-64 (AWG 14/16) P1015-13 (AWG 10/12) Quick connect to screw adaptor P/N: P1015-18 Mounting bracket P/N: P1023-6 DIN rail P/Ns: 017322005 (Steel) C103PM (Al) HRDRGen DIN rail adaptor P/N: P1023-20 10.03.05 See accessory pages for specifications. Low Voltage Products & Systems 5.169