Thermal Overcurrent Circuit Breakers 2-5000/2-5700-...
www.e-t-a.de
1816 1
1
Description
Typical applications
Ordering information
Preferred types
Technical data
Single pole thermal circuit breaker with press-to-reset, tease-free,
trip-free, snap action mechanism. Type 2-5000 is available with optional
manual release (-H), type 2-5700 can be supplied as a push-push
switch/circuit breaker (R-type TO CBE to EN 60934 in press-to-reset
configuration; M-type when fitted with manual release -H; S-type
with push-push operation). Fitted with flange or threadneck for panel
mounting. Options include an additional unprotected circuit tap (-A3).
Approved to CBE standard EN 60934 (IEC 60934).
Motors, transformers, solenoids, battery chargers, power supplies,
appliances, machinery, extra low voltage systems. 2-5000-... 2-5700-...
Type No.
2-5000 flange mounting
2-5700 threadneck panel mounting
Threadneck design – type 2-5700 only
iG1 moulded threadneck 3/8“-27UNS-2A with metal hexnut and
plastic knurled nut (hardware bulk shipped with 5 pcs plus)
iG2 moulded threadneck M12x1 with metal hexnut and plastic
knurled nut (hardware bulk shipped with 5 pcs plus)
Terminal design
P10 blade terminals 6.3-0.8 mm (QC .250)
K10 screw terminals M4x6
Manual release (optional)
H manual release facility (type 2-5000 only)
DD push to release/push to reset (type 2-5700 only)
Current ratings
0.05...25 A
2-5700 - iG1 - P10 - DD - 8 A ordering example
Please be informed that we have minimum ordering quantities to be observed.
Approvals
For further details please see: www.e-t-a.de/ti_e
Voltage rating AC 250 V; DC 28 V
(UL: AC 250 V; DC 50 V)
Current rating range 0.05...25 A
Typical life AC 250 V / DC 28 V:
0.05...16 A 5,000 operations at 2 x IN, inductive
17...25 A 5,000 operations at 2 x IN, resistive
Ambient temperature -20...+60 °C (-4...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity Icn 0.05...2.5 A 8 x IN
3...5 A 20 x IN
6...12 A 200 A
(higher interrupting capacity
available to special order)
13...25 A 300 A
Interrupting capacity IN UN
(UL 1077) 0.05...20 A AC 250 V 2,000 A
0.05...25 A DC 50 V 2,500 A
(higher values upon request)
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 8 g (57-500 Hz) ± 0.61 mm (10-57 Hz),
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
Shock 25 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 29 g
Preferred types Standard current ratings (A)
1 2 3 4 5 6 8 10 12 15 16 20 25
2-5700-IG1-P10- xxxxx xxxxxxxx
2-5700-IG1-P10-DD xxxxxxxxxxx
2-5700-IG2-P10- xxxxxxxxxxx
2-5700-IG2-P10-DD xxxxxxxxxxx
Authority Standard Rated voltage Current ratings
VDE IEC/EN 60934 AC 250 V
DC 28 V 0.05 A…25 A
0.05 A…25 A
UL UL 1077 AC 250 V
DC 50 V 0.05 A…20 A
0.05 A…25 A
CSA C22.2 No 235 AC 250 V
DC 50 V 0.05 A…20 A
0.05 A…25 A
CQC GB 17701 AC 250 V
DC 28 V 0.05 A…25 A
0.05 A…25 A