Thermal Overcurrent Circuit Breaker 3120-F...
www.e-t-a.com06/07(120307)
1- 59
1
Current Internal resistance Current Internal resistance
rating (A) per pole (β¦) rating (A) per pole (β¦)
0.1 94 3.5 0.0565
0.2 24 4 0.0435
0.3 12 4.5 0.0435
0.4 5.30 5 0.0325
0.5 4.20 6 0.0215
0.6 2.90 7 0.0165
0.8 1.50 8 0.0165
1 0.9 10 < 0.02
1.2 0.80 12 < 0.02
1.5 0.45 14 < 0.02
2 0.27 16 < 0.02
2.5 0.0785 18 < 0.02
3 0.0595 20 < 0.02
Description
Typical applications
Approvals
Technical data
An extremely versatile range of rocker switch/thermal circuit breakers (S-
type TO CBE to EN 60934 with trip free mechanism) offering the choice of
single pole, double pole with single pole protection, and double pole with
protection on both poles. Designed for snap-in panel mounting with
versions available for three different panel cut-out sizes. Illumination is
optional and there is a range of colours and markings for the rocker. Under
overload conditions the rocker returns to the OFF position. 6-way frame
for 3120-F5 available upon request.
Any one of the following additional function modules can be supplied
factory fitted to the rear of the switch/circuit breaker.
βUnder voltage release coil (for double pole versions only).
βMagnetic trip coil for short circuit protection.
βMagnetic trip coil for remote relay trip.
βAuxiliary contacts for status signalling.
βMechanical slide interlock.
Approved to CBE standard EN 60934 (IEC 60934).
Motors, transformers, solenoids, extra low voltage wiring systems, office
machines, electro-medical equipment, power supplies, communications
systems, medical equipment to EN 60601.
3120-F...
For further details please see chapter: Technical Information
Voltage rating AC 240 V; DC 50 V
(AC 415 V to special order)
(UL: AC 250 V; DC 50 V)
Current ratings 0.1...20 A
(up to 30 A to special order, single pole only)
Typical life 1-pole
AC 240 V: 0.1...20 A 30,000 operations at 1 x IN, inductive
DC 50 V: 0.1...4 A 30,000 operations at 1 x IN, inductive
4.5...16 A 30,000 operations at 1 x IN, resistive
DC 28 V: 4.5...20 A 30,000 operations at 1 x IN, inductive
2-pole
AC 415 V: 0.1...16 A 10,000 operations at 1 x IN, inductive
AC 240 V: 0.1...16 A 50,000 operations at 1 x IN, inductive
17...20 A 30,000 operations at 1 x IN, inductive
DC 50 V: 0.1...16 A 50,000 operations at 1 x IN, inductive
17...20 A 10,000 operations at 1 x IN, inductive
Ambient temperature -30...+60 Β°C (-22...+140 Β°F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
between poles (2-pole) AC 1,500 V
Insulation resistance > 100 Mβ¦(DC 500 V)
Interrupting capacity Icn 0.1...2 A 10 x IN
2.5...20 A 250 A 2-pole, or 150 A 1-pole
Interrupting capacity INUN2-pole
(UL 1077) 0.1...2 A AC 250 V 200 A
2.5...3 A AC 250 V 1,000 A
3.5...8 A AC 250 V 2,000 A
9...16 A AC 250 V 3,500 A
18...20 A AC 250 V 5,000 A
0.1...20 A DC 50 V 1,000 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) (IP54 with water splash protection)
terminal area IP00
Vibration 8 g (57-500 Hz), Β±0.61 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 30 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH,
to IEC 60068-2-3, test Ca
Mass approx. 33 g (double pole)
approx. 27 g (single pole)
Authority Voltage ratings Current ratings
VDE (EN 60934) AC 240 V; DC 28 V 0.1...20 A
DC 50 V 0.1...20 A 2-pole
DC 50 V 0.1...10 A 1-pole
UL, CSA AC 250 V; DC 50 V 0.1...20 A
CCC AC 250 V; DC 50 V 0.1...20 A
Standard current ratings and typical internal resistance values
Illumination voltage/power consumption
operating voltage power consumption
filament/neon LED
6 V 60 mA 9 mA
12 V 20 mA 9 mA
24 V 20 mA 9 mA
48 V 20 mA 1.5 mA
115 V < 1.5 mA < 1 mA*
230 V < 1.5 mA < 1 mA*
* single pole version only